Article number 6GK7443-1GX20-0XE0 6GK7443-1GX30-0XE0
product type designation CP 443-1 Advanced CP 443-1 Advanced
********** spare part ********* communications processor CP 443-1 Advanced for connection from SIMATIC S7-400 CPU to Industrial Ethernet: PROFINET IO Controller with RT and IRT MRP, PROFINET CBA, TCP/IP, ISO, UDP, S7 comm., S5-compat. comm. (send/receive) fetch/write, with and without RFC1006, multicast, diagnostics extension, SNMP, DHCP, FTP client/server, email, data storage on C-plug, PROFINET interface 4x RJ45 (10/100 Mbit), Gigabit interface 1x RJ45 (10/100/1000 Mbit). Communications processor CP 443-1 Advanced 1x 10/100/1000 Mbps, 4x 10/100 Mbps (IE switch) RJ45 ports; ISO; TCP; UDP; PROFINET IO controller; S7 communication; Open communication (send/receive) S7 routing; IP configuration via DHCP/block; IP access control list; time-of-day synchronization; extended web diagnostics; Fast Startup; PROFIenergy support; IP routing; FTP; Web server; email; please note SIOS ID: 109799025
transfer rate
transfer rate
● at the 1st interface 10 ... 1000 Mbit/s 10 ... 1000 Mbit/s
● at the 2nd interface 10 ... 100 Mbit/s 10 ... 100 Mbit/s
interfaces
number of interfaces / according to Industrial Ethernet 5 5
number of electrical connections
● at the 1st interface / according to Industrial Ethernet 1 1
● at the 2nd interface / according to Industrial Ethernet 4 4
type of electrical connection
● at the 1st interface / according to Industrial Ethernet RJ45 port RJ45 port
● at the 2nd interface / according to Industrial Ethernet RJ45 port RJ45 port
design of the removable storage
● C-PLUG Yes Yes
supply voltage, current consumption, power loss
type of voltage / of the supply voltage DC DC
supply voltage / 1 / from backplane bus 5 V 5 V
supply voltage 5 V
relative symmetrical tolerance / at DC
● at 5 V 5 % 5 %
consumed current
● from backplane bus / at DC / at 5 V / typical 1.8 A 1.8 A
power loss [W] 9 W 9 W
ambient conditions
ambient temperature
● during operation 0 ... 60 °C 0 ... 60 °C
● during storage -40 ... +70 °C -40 ... +70 °C
● during transport -40 ... +70 °C -40 ... +70 °C
relative humidity
● at 25 °C / without condensation / during operation / maximum 95 % 95 %
protection class IP IP20 IP20
design, dimensions and weights
module format Compact module S7-400 single width Compact module S7-400 single width
width 25 mm 25 mm
height 290 mm 290 mm
depth 210 mm 210 mm
net weight 0.7 kg 0.7 kg
product features, product functions, product components / general
number of units
● per CPU / maximum 14 14
● note max. 4 as PN IO ctrl. max. 4 as PN IO ctrl.
performance data / open communication
number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum 64 64
data volume
● as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum 8 Kibyte 8 Kibyte
● as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum 8 Kibyte 8 Kibyte
● as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum 8 Kibyte 8 Kibyte
● as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum 2 Kibyte 2 Kibyte
number of possible connections / for open communication
● by means of T blocks / maximum 64 64
data volume
● as user data per ISO on TCP connection / for open communication / by means of T blocks / maximum 1452 byte 1452 byte
performance data / S7 communication
number of possible connections / for S7 communication
● maximum 128; when using several CPUs 128; when using several CPUs
● with PG connections / maximum 2 2
● with OP connections / maximum 30
performance data / multi-protocol mode
number of active connections / with multi-protocol mode 128 128
performance data / IT functions
number of possible connections
● as client / by means of FTP / maximum 20 20
● as server / by means of FTP / maximum 10 10
number of possible connections
● as server / by means of HTTP / maximum 4 4
● as email client / maximum 1 1
data volume / as user data for email / maximum 8 Kibyte 8 Kibyte
storage capacity / of the user memory
● as flash memory file system 30 Mibyte 30 Mibyte
● as RAM 16 Mibyte 16 Mibyte
● additionally buffered as RAM via central backup battery 512 Kibyte 512 Kibyte
number of possible write cycles / of the flash memory cells 100000 100000
performance data / PROFINET communication / as PN IO controller
product function / PROFINET IO controller Yes Yes
number of PN IO devices / on PROFINET IO controller / operable / total 128 128
number of PN IO IRT devices / on PROFINET IO controller / operable 128 64
number of external PN IO lines / with PROFINET / per rack 4 4
data volume
● as user data for input variables / as PROFINET IO controller / maximum 4 Kibyte 4 Kibyte
● as user data for output variables / as PROFINET IO controller / maximum 4 Kibyte 4 Kibyte
● as user data for input variables per PN IO device / as PROFINET IO controller / maximum 1433 byte 1433 byte
● as user data for output variables per PN IO device / as PROFINET IO controller / maximum 1433 byte 1433 byte
● as user data for input variables per PN IO device / for each sub-module as PROFINET IO controller / maximum 240 byte 240 byte
● as user data for output variables per PN IO device / for each sub-module as PROFINET IO controller / maximum 240 byte 240 byte
performance data / PROFINET CBA
number of remote connection partners / with PROFINET CBA 64
number of connections / with PROFINET CBA / total 600
data volume
● as user data for digital inputs / with PROFINET CBA / maximum 8 Kibyte
● as user data for digital outputs / with PROFINET CBA / maximum 8 Kibyte
● as user data for arrays and data types / in the case of acyclic transmission / with PROFINET CBA / maximum 8 Kibyte
● as user data for arrays and data types / with PROFINET CBA / with cyclical transfer / maximum 250 byte
● as user data for arrays and data types / with PROFINET CBA / in the case of local interconnection / maximum 2400 byte
performance data / PROFINET CBA / remote interconnection / with acyclic transfer
update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA 100 ms
number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum 150
number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum 150
data volume
● as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA 8 Kibyte
● as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA 8 Kibyte
performance data / PROFINET CBA / remote interconnection / with cyclic transfer
update time / of the remote interconnections / with cyclical transfer / with PROFINET CBA 10 ms
number of remote connections to input variables / with PROFINET CBA / with cyclic transfer / maximum 250
number of remote connections to output variables / with cyclical transfer / with PROFINET CBA / maximum 250
data volume
● as user data for remote interconnections with input variables / with cyclical transfer / with PROFINET CBA / maximum 2000 byte
● as user data for remote interconnections with output variables / with cyclical transfer / with PROFINET CBA / maximum 2000 byte
performance data / PROFINET CBA / HMI variables via PROFINET / acyclic
number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA 3
update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA 500 ms
number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum 200
data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum 8 Kibyte
performance data / PROFINET CBA / device-internal interconnections
number of internal connections / with PROFINET CBA / maximum 300
data volume / of the internal connections / with PROFINET CBA / maximum 2400 byte
performance data / PROFINET CBA / interconnections to constants
number of connections with constants / with PROFINET CBA / maximum 500
data volume / as user data for interconnections with constants / with PROFINET CBA / maximum 4000 byte
performance data / PROFINET CBA / PROFIBUS proxy functionality
product function / with PROFINET CBA / PROFIBUS proxy functionality No
product functions / management, configuration, engineering
product function / MIB support Yes Yes
protocol / is supported
● SNMP v1 Yes Yes
● SNMP v3 Yes
● DCP Yes Yes
● LLDP Yes Yes
configuration software
● required STEP 7 V5.4 SP4 or higher STEP 7 V5.5 SP3 or higher / STEP 7 Professional V12 (TIA Portal) or higher
● for PROFINET CBA / required SIMATIC iMap V3.0 SP1 and higher
product function / is supported / identification link Yes
product functions / diagnostics
product function / web-based diagnostics Yes Yes
product functions / switch
product feature / switch Yes Yes
product function
● switch-managed No No
● with IRT / PROFINET IO switch Yes Yes
● configuration with STEP 7 Yes Yes
product functions / redundancy
product function
● ring redundancy Yes Yes
● redundancy manager Yes Yes
protocol / is supported / Media Redundancy Protocol (MRP) Yes Yes
product functions / security
firewall version stateful inspection
product function / with VPN connection IPSec
type of encryption algorithms / with VPN connection AES-256, AES-192, AES-128, 3DES-168, DES-56
type of authentication procedure / with VPN connection Preshared key (PSK), X.509v3 certificates
type of hashing algorithms / with VPN connection MD5, SHA-1
number of possible connections / with VPN connection 32
product function
● password protection for Web applications Yes Yes
● ACL - IP-based Yes Yes
● ACL - IP-based for PLC/routing Yes Yes
● switch-off of non-required services Yes Yes
● blocking of communication via physical ports Yes Yes
● log file for unauthorized access No No
product functions / time
product function / SICLOCK support Yes Yes
product function / pass on time synchronization Yes Yes
protocol / is supported
● NTP Yes Yes
standards, specifications, approvals / hazardous environments
certificate of suitability / CCC / for hazardous zone according to GB standard Yes; GB3836.1, GB3836.8
certificate of suitability / CCC / for hazardous zone according to GB standard / as marking Ex nA IIC T4 Gc
standards, specifications, approvals / Environmental Product Declaration
Environmental Product Declaration Yes
Global Warming Potential [CO2 eq]
● total 350.22 kg
● during manufacturing 65.61 kg
● during operation 281.89 kg
● after end of life 2.72 kg
further information / internet links
internet link
● to web page: selection aid TIA Selection Tool http://www.siemens.com/tia-selection-tool
● to website: Industrial communication http://www.siemens.com/simatic-net
● to website: Image database http://automation.siemens.com/bilddb https://www.automation.siemens.com/bilddb
● to website: CAx-Download-Manager http://www.siemens.com/cax
● to website: Industry Online Support https://support.industry.siemens.com https://support.industry.siemens.com
security information
security information Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7) Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7)
Approvals / Certificates
General Product Approval
Manufacturer Declaration Yes Yes
EU declaration of conformity EU declaration of conformity Yes Yes
UL UL
Yes Yes
KC Yes Yes
RCM RCM
Yes Yes
For use in hazardous locations
ATEX ATEX Yes Yes
FM Yes Yes
UL UL
Yes Yes
IECEx IECEx
Yes Yes
Type Examination Certificate Yes Yes
Marine / Shipping
BV (Bureau Veritas) BV (Bureau Veritas) Yes Yes
DNV (Det Norske Veritas) DNV (Det Norske Veritas) Yes Yes
PRS (Polski Register of Shipping) PRS (Polski Register of Shipping) Yes Yes
CCS (China Classification Society) Yes Yes
Environment
Confirmation Yes Yes
last modified: 3/22/2024
Date
3/25/2024
Subject to change without notice