Article number 6EP1336-3BA00 6EP1336-3BA10
SITOP Modular/1AC/DC24V/20A SITOP PSU8200/1ACDC/24VDC/20A
SITOP modular 20 A Stabilized power supply input: 120/230 V AC output: 24 V DC/20 A SITOP PSU8200 20 A stabilized power supply input: 120-230 V AC 110-220 V DC output: 24 V DC/20 A
input
type of the power supply network 1-phase AC 1-phase and 2-phase AC or DC
supply voltage at AC
● minimum rated value 120 V
● maximum rated value 230 V
● initial value 85 V
● full-scale value 275 V
supply voltage at AC Set by means of wire jumper on the device; starting from Vin > 93/183 V temperature derating necessary at Uin<100 V AC or DC at 50 °C; additional derating at Uin<100 V: Uin=95 V Pa max=460 W, Uin=90 V Pa max=440 W, Uin=85 V Pa max=420 W
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 176 ... 264 V
supply voltage at DC 110 ... 220 V
input voltage at DC 88 ... 350 V
wide range input No Yes
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of power failure minimum 20 ms 20 ms
operating condition of the mains buffering at Vin = 230 V at Vin = 230 V
line frequency 50/60 Hz 50/60 Hz
line frequency 47 ... 63 Hz 47 ... 63 Hz
input current
● at rated input voltage 120 V 7.7 A 4.6 A
● at rated input voltage 230 V 3.5 A 2.5 A
current limitation of inrush current at 25 °C maximum 60 A 20 A
I2t value maximum 9.9 A²·s 5 A²·s
fuse protection type Yes Yes
fuse protection type in the feeder Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2411-1JA10 (120 V) or 3RV2411-1FA10 (230 V) Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V
output
voltage curve at output Controlled, isolated DC voltage Controlled, isolated DC voltage
output voltage at DC rated value 24 V 24 V
output voltage
● at output 1 at DC rated value 24 V 24 V
output voltage adjustable Yes; via potentiometer Yes; via potentiometer
adjustable output voltage 24 ... 28.8 V 24 ... 28 V
relative overall tolerance of the voltage 3 % 3 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 % 0.1 %
● on slow fluctuation of ohm loading 0.1 % 0.3 %
residual ripple
● maximum 100 mV 100 mV
● typical 30 mV 80 mV
voltage peak
● maximum 200 mV 200 mV
● typical 60 mV 100 mV
display version for normal operation Green LED for 24 V OK Green LED for 24 V OK
type of signal at output via signaling module (6EP1961-3BA10) Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on Overshoot of Vout approx. 3 % No overshoot of Vout (soft start)
response delay maximum 0.1 s 1.5 s
voltage increase time of the output voltage
● typical 50 ms 250 ms
output current
● rated value 20 A 20 A
● rated range 0 ... 20 A; +60 ... +70 °C: Derating 3.5%/K 0 ... 20 A; +60 ... +70 °C: Derating 3%/K
supplied active power typical 480 W 480 W
short-term overload current
● at short-circuit during operation typical 60 A 60 A
duration of overloading capability for excess current
● at short-circuit during operation 25 ms 25 ms
constant overload current
● on short-circuiting during the start-up typical 23 A 30 A
bridging of equipment Yes; switchable characteristic Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power 2 2
efficiency in percent 89 % 94 %
power loss [W]
● at rated output voltage for rated value of the output current typical 59 W 31 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 1 % 0.5 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 2 % 1 %
setting time
● load step 50 to 100% typical 2 ms 1 ms
● load step 100 to 50% typical 2 ms 1 ms
setting time
● maximum 5 ms 5 ms
protection and monitoring
design of the overvoltage protection < 35 V < 31.8 V
property of the output short-circuit proof Yes Yes
design of short-circuit protection Alternatively, constant current characteristic approx. 23 A or latching shutdown Alternatively, constant current characteristic approx. 21.5 A or latching shutdown
● typical 23 A 21.5 A
overcurrent overload capability
● in normal operation overload capability 150 % Iout rated up to 5 s/min
enduring short circuit current RMS value
● typical 23 A 21.5 A
display version for overload and short circuit LED yellow for "overload", LED red for "latching shutdown" LED yellow for "overload", LED red for "latching shutdown"
safety
galvanic isolation between input and output Yes Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 SELV (ES1) output voltage Ua according to EN 61204-7, transformer according to EN 61558-2-16
operating resource protection class Class I Class I
leakage current
● maximum 3.5 mA 3.5 mA
● typical 0.4 mA 1 mA
protection class IP IP20 IP20
standard
● for emitted interference EN 55022 Class B EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2 EN 61000-3-2
● for interference immunity EN 61000-6-2 EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 62368-1, UL 62368-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 62368-1, UL 62368-1)
● UKCA marking Yes
● EAC approval Yes Yes
● Regulatory Compliance Mark (RCM) Yes Yes
● NEC Class 2 No No
● SEMI F47 Yes Yes
type of certification
● BIS Yes; R-41183539
● CB-certificate No Yes
MTBF at 40 °C 786 164 h 583 500 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No No
● ATEX No No
● ULhazloc approval No No
● cCSAus, Class 1, Division 2 No No
● FM registration No No
standards, specifications, approvals marine classification
shipbuilding approval Yes Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes Yes
● French marine classification society (BV) No No
● Det Norske Veritas (DNV) Yes Yes
● Lloyds Register of Shipping (LRS) No No
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes Yes
Global Warming Potential [CO2 eq]
● total 1 881.8 kg 989.5 kg
● during manufacturing 34.7 kg 18.9 kg
● during operation 1 846.1 kg 970 kg
● after end of life 0.5 kg 0.27 kg
ambient conditions
ambient temperature
● during operation 0 ... 70 °C; with natural convection -25 ... +70 °C; With natural convection; startup tested starting from -40 °C nominal voltage
● during transport -40 ... +85 °C -40 ... +85 °C
● during storage -40 ... +85 °C -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation Climate class 3K3, 5 … 95% no condensation
connection method
type of electrical connection screw terminal screw terminal
● at input L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded L, N, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded
● at output +, -: 2 screw terminals each for 0.5 ... 4 mm² +, -: 2 screw terminals each for 0.2 ... 4 mm²
● for auxiliary contacts - 13, 14 (alarm signal), 15, 16 (Remote ON OFF): 1 screw terminal each for 0.14 ... 1.5 mm²
mechanical data
width × height × depth of the enclosure 160 × 125 × 125 mm 90 × 125 × 125 mm
installation width × mounting height 160 × 225 mm 90 × 225 mm
required spacing
● top 50 mm 50 mm
● bottom 50 mm 50 mm
● left 0 mm 0 mm
● right 0 mm 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15 Snaps onto DIN rail EN 60715 35x7.5/15
● standard rail mounting Yes Yes
● S7 rail mounting No No
● wall mounting No No
housing can be lined up Yes Yes
net weight 2.2 kg 1.2 kg
accessories
electrical accessories Buffer module, signaling module Buffer module
mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
further information internet links
internet link
● to web page: selection aid TIA Selection Tool https://siemens.com/tst https://siemens.com/tst
● to website: Industrial communication http://www.siemens.com/simatic-net http://www.siemens.com/simatic-net
● to website: CAx-Download-Manager http://www.siemens.com/cax http://www.siemens.com/cax
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
security information
security information Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7) Siemens provides products and solutions with industrial cybersecurity functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial cybersecurity concept. Siemens’ products and solutions constitute one element of such a concept. Customers are responsible for preventing unauthorized access to their plants, systems, machines and networks. Such systems, machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures (e.g. firewalls and/or network segmentation) are in place. For additional information on industrial cybersecurity measures that may be implemented, please visit www.siemens.com/cybersecurity-industry. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Cybersecurity RSS Feed under https://www.siemens.com/cert. (V4.7)
Classifications
Version Classification
eClass 14 27-04-07-01
eClass 12 27-04-07-01
eClass 9.1 27-04-07-01
eClass 9 27-04-07-01
eClass 8 27-04-90-02
eClass 7.1 27-04-90-02
eClass 6 27-04-90-02
ETIM 9 EC002540
ETIM 8 EC002540
ETIM 7 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04
Version Classification
eClass 14 27-04-07-01
eClass 12 27-04-07-01
eClass 9.1 27-04-07-01
eClass 9 27-04-07-01
eClass 8 27-04-90-02
eClass 7.1 27-04-90-02
eClass 6 27-04-90-02
ETIM 9 EC002540
ETIM 8 EC002540
ETIM 7 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04
Approvals Certificates
General Product Approval
CSA CSA
Yes Yes
Manufacturer Declaration Yes Yes
Declaration of Conformity Yes Yes
UK Declaration of Conformity UK Declaration of Conformity
Yes Yes
UL UL
Yes Yes
UR UR
Yes Yes
Miscellaneous Yes Yes
RCM RCM
Yes Yes
For use in hazardous locations
ATEX ATEX Yes Yes
CCC-Ex Yes Yes
Marine / Shipping
ABS (American Bureau of Shipping) ABS (American Bureau of Shipping)
Yes Yes
DNV (Det Norske Veritas) DNV (Det Norske Veritas) Yes Yes
Environment
EPD Typ II/III (with life cylce assessment) EPD Typ II/III (with life cylce assessment) Yes Yes
last modified: 4/8/2024
Date
4/19/2024
Subject to change without notice
© Copyright Siemens 2024