Article number 6EP1353-2BA00 6EP3343-0SA00-0AY0
SITOP FLEXI 120 W SITOP PSU3600 FLEXI/1AC/3-52VDC/10A/120W
********* spare part ********** SITOP power FLEXI stabilized power supply input: 120/230 V AC output: 3-52 V DC/10 A, 120 W SITOP PSU3600 flexi Stabilized power supply Input: 120-230 V AC Output: 3-52 V DC/10 A, 120 W
Input
type of the power supply network 1-phase AC 1-phase AC or DC
supply voltage at AC
● minimum rated value 120 V 120 V
● maximum rated value 230 V 230 V
● initial value Set via wire jumper 85 V; Derating at < 110 V AC/DC: output power max. 100 W
● full-scale value 264 V
supply voltage
● 1 at AC rated value 120 V
● 2 at AC rated value 230 V
● at DC 110 ... 220 V
input voltage
● 1 at AC 85 ... 132 V
● 2 at AC 170 ... 264 V
● at DC 88 ... 250 V
design of input wide range input No Yes
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
operating condition of the mains buffering at Pout = 120 W and Vin = 93/187 V With Pa = 120 W and Ue = 230 V AC
buffering time for rated value of the output current in the event of power failure minimum 10 ms 80 ms
operating condition of the mains buffering at Pout = 120 W and Vin = 93/187 V With Pa = 120 W and Ue = 230 V AC
line frequency
● 1 rated value 50 Hz 50 Hz
● 2 rated value 60 Hz 60 Hz
line frequency 47 ... 63 Hz 47 ... 63 Hz
input current
● at rated input voltage 120 V 2.2 A 2.6 A
● at rated input voltage 230 V 0.9 A 1.3 A
● at rated input voltage 110 V 1.3 A
● at rated input voltage 220 V 0.7 A
current limitation of inrush current at 25 °C maximum 32 A 35 A
I2t value maximum 0.8 A²·s 1 A²·s
fuse protection type T 3,15 A/250 V (not accessible) T 3.15 A (not accessible)
● in the feeder Recommended miniature circuit breaker: from 6 A characteristic C Recommended miniature circuit breaker: 6-10 A characteristic C
Output
voltage curve at output Controlled, isolated DC voltage Controlled, isolated DC voltage
output voltage at DC rated value 24 V 24 V
formula for output voltage 3-52 V DC 3-52 V DC
output voltage
● at output 1 at DC rated value 24 V 24 V
relative overall tolerance of the voltage 1 % 1 %
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 % 0.1 %
● on slow fluctuation of ohm loading 0.2 % 1 %
voltage compensation per sense line 0.5 V 0.5 V
residual ripple
● maximum 50 mV 50 mV
● typical 20 mV
voltage peak
● maximum 100 mV 100 mV
● typical 80 mV
adjustable output voltage 3 ... 52 V 0 ... 52 V
product function output voltage adjustable Yes Yes
type of output voltage setting via potentiometer or analog current voltage signal 0 ... 2.5 V via potentiometer (setting range 3 to 52 V) or analog control voltage signal 0 to 2.5 V (setting range 0 to 52 V)
display version for normal operation Green LED for 24 V OK Two-color LED: green for 24 V o.k., red for overload
type of signal at output Power-Good via relay contact, current monitor signal 0 … 2.5 V DC OK via relay contact, current monitor signal (0 to 2.5 V correspond to 0 to 10 A)
behavior of the output voltage when switching on No overshoot of Vout (soft start) No overshoot of Vout (soft start)
response delay maximum 3 s 0.5 s
voltage increase time of the output voltage
● typical 80 ms 20 ms
output current
● rated value 10 A 10 A
● minimum rated value 2 A
● maximum rated value 10 A
● rated range 0 ... 10 A; max. 120 W 0 ... 10 A; Output power max. 120 W
supplied active power typical 120 W 120 W
constant overload current
● on short-circuiting during the start-up typical 10 A 12 A
● at short-circuit during operation typical 10 A 12 A
product feature
● bridging of equipment Yes Yes
number of parallel-switched equipment resources for increasing the power 2 2
Efficiency
efficiency in percent 84 % 88 %
power loss [W]
● at rated output voltage for rated value of the output current typical 23 W 16 W
● during no-load operation maximum 3 W
Closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical 0.3 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical 5 %
setting time
● maximum 0.2 ms
Protection and monitoring
design of the overvoltage protection Yes, according to EN 60950-1 ≤ 60 V according to EN 60950-1
response value current limitation 2 ... 10 A 2 ... 10 A
design of the current limitation 2 ... 10 A, adjustable using potentiometer or analog control voltage signal 0 ... 2.5 V Can be set with potentiometer or analog control voltage signal 0.5 ... 2.5 V
property of the output short-circuit proof Yes Yes
design of short-circuit protection Electronic current limiting (2 ... 10 A) in the range 3 ... 12 V or power limiting (120 W) in the range 12 ... 52 V Electronic current limiting (2 ... 10 A) in the range 3 ... 12 V or power limiting (120 W) in the range 12 ... 52 V
enduring short circuit current RMS value
● maximum 12 A
overcurrent overload capability in normal operation According to the adjusted current regulation 2 ... 10 A
display version for overload and short circuit Red LED for current or power limiting
Safety
galvanic isolation between input and output Yes Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 Safety extra low output voltage Vout according to EN 60950-1
operating resource protection class Class I Class I
leakage current
● maximum 3.5 mA 3.5 mA
protection class IP IP20 IP20
Approvals
certificate of suitability
● CE marking Yes Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● CSA approval No; - No; -
● cCSAus, Class 1, Division 2 No No
● ATEX No No
certificate of suitability
● IECEx No No
● NEC Class 2 No No
● ULhazloc approval No No
● FM registration No No
type of certification CB-certificate No Yes
certificate of suitability
● EAC approval Yes Yes
● C-Tick No Yes
● Regulatory Compliance Mark (RCM) Yes
certificate of suitability shipbuilding approval No No
shipbuilding approval - -
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) No No
● French marine classification society (BV) No No
● DNV GL No No
● Lloyds Register of Shipping (LRS) No No
● Nippon Kaiji Kyokai (NK) No No
EMC
standard
● for emitted interference EN 55022 Class B EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2 EN 61000-3-2
● for interference immunity EN 61000-6-2 EN 61000-6-2
environmental conditions
ambient temperature
● during operation 0 ... 60 °C; with natural convection -25 ... +70 °C; Derating > 60°C: 2%/°K
● during transport -40 ... +85 °C -40 ... +85 °C
● during storage -40 ... +85 °C -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 … 95% no condensation Climate class 3K3, 5 … 95% no condensation
Mechanics
type of electrical connection screw-type terminals screw-type terminals
● at input L1, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded L1, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
● at output L+: 1 screw terminal for 0.5 ... 2.5 mm²; M: 2 screw terminals for 0.5 ... 2.5 mm² +, -: 2 screw terminals each for 0.5 ... 2.5 mm² single-core/finely stranded
● for auxiliary contacts Alarm signals, control inputs: 1 screw terminal each for 0.14 ... 1.5 mm² Alarm signals, control inputs: screw-type terminals for 0.14 ... 1.5 mm² single-core/finely stranded
width of the enclosure 75 mm 42 mm
height of the enclosure 125 mm 125 mm
depth of the enclosure 125 mm 135 mm
required spacing
● top 50 mm 50 mm
● bottom 50 mm 50 mm
● left 0 mm 0 mm
● right 0 mm 0 mm
net weight 0.9 kg 0.55 kg
product feature of the enclosure housing can be lined up Yes Yes
fastening method Snaps onto DIN rail EN 60715 35x7.5/15 Snaps onto DIN rail EN 60715 35x7.5/15
MTBF at 40 °C 1 196 172 h 1 200 000 h
other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)