Article number |
6EP1733-2BA00-0AA0
|
6EP3233-0TA00-0AY0
|
|
|
|
|
SITOP PSU400S/DC/DC/48V/24V/5A |
SITOP PSU3400/DC/DC/48V/24V/5A |
|
********* spare part ********** SITOP PSU400S 24 V/5 A stabilized power supply input: 48 V DC (30.2...75 V) output: 24 V DC/5 A (22...28V) |
SITOP PSU3400 24 V/5 A Stabilized power supply Input: 48 V DC (28…60 V) Output: 24 V DC/5 A |
Input |
type of the power supply network |
DC voltage |
DC voltage |
supply voltage at AC |
|
● initial value |
|
Startup as of 36 V, derating necessary for 28 ... 36 V DC |
supply voltage |
|
● at DC |
|
48 ... 48 V |
input voltage |
|
● at DC |
30 ... 75.5 V |
28 ... 60 V |
design of input wide range input |
|
No |
overvoltage overload capability |
|
- |
operating condition of the mains buffering |
at Vin = 48 V |
at Vin = 48 V |
buffering time for rated value of the output current in the event of power failure minimum |
5 ms |
5 ms |
operating condition of the mains buffering |
at Vin = 48 V |
at Vin = 48 V |
input current |
|
● at rated input voltage 48 V |
2.9 A |
2.7 A |
current limitation of inrush current at 25 °C maximum |
|
15 A |
I2t value maximum |
|
0.12 A²·s |
fuse protection type |
|
15 A (not accessible), breaking capacity 100 A |
● in the feeder |
6 A characteristic C |
Recommended miniature circuit breaker: 16 A characteristic B or C |
Output |
voltage curve at output |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
output voltage at DC rated value |
24 V |
24 V |
output voltage |
|
● at output 1 at DC rated value |
24 V |
24 V |
relative overall tolerance of the voltage |
3 % |
1 % |
relative control precision of the output voltage |
|
● on slow fluctuation of input voltage |
|
0.1 % |
● on slow fluctuation of ohm loading |
|
0.3 % |
residual ripple |
|
● maximum |
50 mV |
150 mV |
● typical |
|
70 mV |
voltage peak |
|
● maximum |
200 mV |
250 mV |
● typical |
|
220 mV |
adjustable output voltage |
22.8 ... 28 V |
24 ... 28 V |
product function output voltage adjustable |
Yes |
Yes |
type of output voltage setting |
via potentiometer; max. 120 W |
via potentiometer |
display version for normal operation |
Green LED for 24 V OK |
Green LED for 24 V OK |
type of signal at output |
No |
|
behavior of the output voltage when switching on |
|
No overshoot of Vout (soft start) |
response delay maximum |
2.5 s |
0.5 s |
voltage increase time of the output voltage |
|
● typical |
|
10 ms |
● maximum |
1 500 ms |
20 ms |
output current |
|
● rated value |
5 A |
5 A |
● rated range |
0 ... 5 A; +60 ... +70 °C: Derating 2.5%/K |
0 ... 6 A; 6 A up to +40°C; +60 ... +70 °C: Derating 2%/K |
supplied active power typical |
120 W |
130 W |
product feature |
|
● bridging of equipment |
Yes |
Yes |
number of parallel-switched equipment resources for increasing the power |
2 |
2 |
Efficiency |
efficiency in percent |
89 % |
92 % |
power loss [W] |
|
● at rated output voltage for rated value of the output current typical |
5 W |
10 W |
● during no-load operation maximum |
|
1.5 W |
Closed-loop control |
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical |
|
0.3 % |
relative control precision of the output voltage load step of resistive load 50/100/50 % typical |
|
2 % |
setting time |
|
● load step 50 to 100% typical |
|
1 ms |
● load step 100 to 50% typical |
|
1 ms |
setting time |
|
● maximum |
1 ms |
|
Protection and monitoring |
design of the overvoltage protection |
< 33 V |
Ua < 35 V |
response value current limitation typical |
|
6.5 A |
property of the output short-circuit proof |
Yes |
Yes |
design of short-circuit protection |
|
Electronic shutdown, automatic restart |
overcurrent overload capability in normal operation |
overload capability 150 % Iout rated up to 5 s/min |
|
display version for overload and short circuit |
|
Yellow LED overload |
Safety |
galvanic isolation between input and output |
Yes |
Yes |
galvanic isolation |
Safety extra low output voltage Vout according to EN 60950-1 |
Safety extra low output voltage Vout according to EN 60950-1 |
operating resource protection class |
|
Class III |
protection class IP |
|
IP20 |
Approvals |
certificate of suitability |
|
● CE marking |
Yes |
Yes |
● UL approval |
Yes; UL 508, CSA C22.2 No. 107.1 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
● CSA approval |
Yes; UL 508, CSA C22.2 No. 107.1 |
Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259 |
● cCSAus, Class 1, Division 2 |
No |
No |
● ATEX |
No |
No |
certificate of suitability |
|
● IECEx |
No |
No |
● NEC Class 2 |
No |
No |
● ULhazloc approval |
No |
No |
● FM registration |
No |
No |
type of certification CB-certificate |
|
Yes |
certificate of suitability |
|
● EAC approval |
Yes |
Yes |
● Regulatory Compliance Mark (RCM) |
|
Yes |
certificate of suitability shipbuilding approval |
No |
Yes |
shipbuilding approval |
- |
ABS, DNV GL |
Marine classification association |
|
● American Bureau of Shipping Europe Ltd. (ABS) |
No |
Yes |
● French marine classification society (BV) |
No |
No |
● DNV GL |
No |
Yes |
● Lloyds Register of Shipping (LRS) |
No |
No |
● Nippon Kaiji Kyokai (NK) |
No |
No |
EMC |
standard |
|
● for emitted interference |
EN 61000-6-3 Class A |
EN 61000-6-3 |
● for mains harmonics limitation |
|
not applicable |
● for interference immunity |
EN 61000-6-2 |
EN 61000-6-2 |
environmental conditions |
ambient temperature |
|
● during operation |
-25 ... +70 °C; with natural convection |
-25 ... +70 °C; with natural convection |
● during transport |
-40 ... +85 °C |
-40 ... +85 °C |
● during storage |
-40 ... +85 °C |
-40 ... +85 °C |
environmental category according to IEC 60721 |
Climate class 3K3, 5 … 95% no condensation |
Climate class 3K3, 5 … 95% no condensation |
Mechanics |
type of electrical connection |
screw-type terminals |
screw-type terminals |
● at input |
+, -: 1 screw terminal each for 0.2 ... 2.5 mm² |
L, N, FE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded |
● at output |
+, -: 2 screw terminals each for 0.2 ... 2.5 mm² |
+, -: 2 screw terminals each for 0.5 ... 2.5 mm² |
width of the enclosure |
50 mm |
32 mm |
height of the enclosure |
125 mm |
100 mm |
depth of the enclosure |
125 mm |
100 mm |
required spacing |
|
● top |
50 mm |
50 mm |
● bottom |
50 mm |
50 mm |
● left |
0 mm |
0 mm |
● right |
0 mm |
0 mm |
net weight |
0.5 kg |
0.32 kg |
product feature of the enclosure housing can be lined up |
Yes |
Yes |
fastening method |
Snaps onto DIN rail EN 60715 35x7.5/15 |
Snaps onto DIN rail EN 60715 35x7.5/15 |
electrical accessories |
Redundancy module, buffer module, diagnostics module SITOP select, DC UPS |
Buffer module |
MTBF at 40 °C |
500 000 h |
1 965 061 h |
other information |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |