ENG_393765.XML
SIMATIC ET 200MP features a variable and scalable station configuration. The maximum configuration is 30 I/O modules with a max. of 1440 input bytes and output bytes each per station.
The compact dimensions of the SIMATIC ET 200MP mean that it can be fitted without any problems in the existing mounting space of a SIMATIC S7-300 PLC or an ET 200M I/O system.
The overall width of the interface module and the individual I/O modules is 35 mm, modules with a width of 25 mm are also available.
The ease with which the modules can be joined using a U-connector saves time during installation. Installation is on an S7-1500 aluminum rail. This can be ordered in various lengths, including a 2-meter rail which you can shorten as desired to optimally use the space available. The integrated DIN rail allows snapping-on of many standard components such as additional terminals, miniature circuit breakers or small relays.
As an option, the active backplane bus can be used instead of the U-connector. This is used whenever high plant availability is required, for example with 24/7 processes. Like the U-connector, the active backplane bus is installed in the regular S7-1500 aluminum rail and then fitted with the modules. Versions with 4, 8 and 12 slots for I/O modules are available.
The I/O signals are connected via a 40-pin front connector. This permits the connection of conductors with a cross-section from 0.25 mm2 to 1.5 mm2 (AWG 24 to AWG 16). Front connectors with screw-type terminals and push-in terminals are available for 35-mm modules; front connectors with push-in terminals are available for 25-mm modules.
To allow simple wiring of the front connector, it can be set to a "prewiring position". In this position, the connector does not yet have any contact with the module. This position can also be used to make changes during operation. The user is supported by a printed cabling diagram on the inside of the front flap.
The mechanical coding prevents destruction of the electronics by accidental incorrect insertion. The result is a higher fail-safety.
The IM155-5 PN ST, IM 155-5 PN HF and IM 155-5 MF HF interface modules of the SIMATIC ET 200MP I/O system are designed in such a way that a station can be equipped with up to 12 I/O modules. By adding a system power supply (PS), up to 30 I/O modules can be operated within one station. Simple retrofitting of I/O modules is thus possible without having to adapt and reconfigure the PROFINET network.
A system power supply (PS) is not required for the interface modules IM155-5 DP ST (PROFIBUS) and IM 155-5 PN BA (PROFINET). Here, up to 12 I/O modules can be operated within a station.
Labeling strips are available for the SIMATIC ET 200MP I/O modules. These DIN A4 sheets can be printed using a standard laser printer. An automatic printout can be produced from TIA Portal without having to reenter the symbols or addresses. The labeling strips are designed such that the assignment between the inscription and the channel or diagnostics display is 1:1. This 1:1 assignment between the inscription and the terminal is retained when the front flap is opened.
Interface module
The interface module connects SIMATIC ET 200MP with PROFINET, Ethernet /IP, Modbus TCP or PROFIBUS and exchanges data between the higher-level controller and the I/O modules.
The IM 155-5 MF HF interface module for Ethernet-based fieldbuses can be connected via BusAdapters using various connection methods and transmission media.
I/O modules
The following module types are available for use on SIMATIC ET 200MP:
- Digital input modules; 16, 32 or 64 channels; 24 V DC; 230 V AC; sinking/sourcing input; universal wide range module from 24 V ... 125 V
- Digital output modules; 8, 32, 16 or 64 channels; 24 V DC; 230 V AC; rated current 0.3 A, 0.5 A, 1 A, 2 A or 5 A per channel; universal wide range module from 24 V to 125 V
- Analog input modules; 4, 8 or 16 channels; measurement types: Current, voltage, resistance, resistance thermometer; thermocouple; an analog input module with the HART protocol is also available
- Analog output modules; 2, 4 or 8 channels; output ranges: Current, voltage; an analog output module with the HART protocol is also available
- Of particular note are the High Speed (HS) analog modules with an extremely short conversion time of 62.5 µs (AI) or 125 µs (AQ) for 8 channels
- Technology modules for counting, positioning, and for fast preprocessing with very short response times under one microsecond (TM FAST)
- Integrated technological functions, such as counting, PWM or switching cycle counters, for selected modules
- Communications modules for IO-Link and point to point communication
- Selected analog input modules suitable for applications in accordance with the AMS2750E and CQI-9 standards in the aerospace or automotive industry
- Safety-related load group shutdown in accordance with SILCL 2 for selected digital output modules via an external 3SK ... safety relay
- F-modules for safety applications: F-DI 16x24VDC, F-DQ 8x24VDC/2A PPM and F-AI 8xI 0(4)..20mA
Various module classes are available to provide users with optimum scalability in their application. The modules themselves are labeled accordingly:
- BA (Basic): Simple, cost-effective modules, without diagnostics and without parameters
- ST (Standard): Modules with module-granular or load group-granular diagnostics and with parameters if applicable; for analog modules: Accuracy class 0.3%
- HF (High Feature): Modules with channel-granular diagnostics and parameter settings; for analog modules: Accuracy class 0.1%, increased immunity and galvanic isolation
- HS (High Speed): Modules with extremely short filter and conversion times for very fast applications; e.g. 8-channel analog modules with a conversion time of 125 µs
Extended functions
Some modules feature extended functions which facilitate simple and low-cost entry into the technology functions.
The two High Feature digital input modules enable simple acquisition of count pulses with a frequency of up to 6 kHz on two of the 16 or 32 inputs. The High Speed digital input permits a counting frequency of up to 20 kHz.
The two 24 V digital High Feature modules and the 230 V AC TRIAC modules have one integrated switching cycle counter per channel, which allows the number of switching cycles to be captured for a connected actuator. This means they can be replaced prior to the end of their service life to avoid downtimes and increase plant availability. The two relay modules also have a built-in counter to record the switching cycles of the integrated relays. When a user-defined limit is reached, a maintenance alarm is triggered and the user can replace the module if necessary before it fails due to wear (preventive maintenance).
The 2 A digital output module has two channels which can be used for pulse width modulation (PWM) with a max. frequency of up to 500 Hz.
Extended functions are also available for analog modules:
The temporal resolution can be increased by "Oversampling" in isochronous mode to enable finer resolution of the signal sequences.
The "Measuring range scaling" function enables the precise resolution of the measured signal around a specific operating point to several decimal places.
With "Measured value scale", a technological variable can be directly assigned to the analog value of the module. The conversion is made directly in the module, which saves power and cycle time in the CPU.
Simple and fast diagnostics using quality information directly in the user program
By activating the quality information (QI) of a module, the validity of the delivered process value can be directly scanned and evaluated in the user program. Access is possible using simple binary or load commands via the process image. The prerequisite is that the module can be diagnosed and the quality information can be configured in TIA Portal.
Manuals
Manuals for the scalable ET 200MP I/O system can be downloaded free of charge from the internet (see SIMATIC Customer Support at this link). These are available individually for each module. The "Manual Collection" also provides you with a PDF file as a compendium, which includes all manuals required for the system.
Accessories
- Labeling sheets for 35-mm modules
For insertion into the I/O modules. 10 DIN A4 sheets with 10 strips each, perforated, for printing using a standard laser printer; colors available: Al gray, yellow (for F-modules)
- Labeling sheets for 25-mm modules
For insertion into the I/O modules. 10 DIN A4 sheets with 20 strips each, perforated, for printing using a standard laser printer; colors available: Al gray
- Shield connection for 35-mm modules
A shield connection set which can be easily mounted without tools is available for the ET 200MP system (analog modules and technology modules). This consists of a 24 V DC infeed element, a shielding bracket, and a universal shield terminal. The latter is designed so that it can be used for a single thin trunk cable, several thin trunk cables, or a thick trunk cable. Consistent separation of 24 V DC infeed and measured signals as well as a low-impedance connection between shield and signal cables ensure high EMC stability and high resistance to interference.
- Front connector for 35 mm modules
Standardized 40-pin front connector for connecting the I/O signals; available with screw-type and push-in terminal systems
- Front connector for 25 mm modules
Standardized 40-pin front connector for connecting the I/O signals; available with push-in system; for simplified ordering and logistics, this plug is enclosed with every 25 mm wide I/O module. It can also be ordered as a spare part.
- SIMATIC TOP connect in different versions for a large number of S7-1500 IO modules; the 64-channel modules are connected exclusively using this version.
- DIN rail adapter
For mounting an S7-1500 mounting rail in control and terminal boxes with integrated 35 mm DIN rail
- Miscellaneous
Further accessories are also available, such as front flaps for the I/O modules, power supplies, communication and technology modules or U-connectors for the self-configuring backplane bus.
Installation
SIMATIC ET 200MP has a design with front connectors ("quasi-permanent wiring"). The front connector is plugged onto the I/O module. When replacing a module, only the front connector must be released from the module. Rewiring of the actual signals is unnecessary. This guarantees fast replacement of modules. The integrated mechanical slot coding prevents inadvertent interchanging of the front connectors.
Only SIMATIC TOP connect is used for the 64-channel modules.
ENG_393766.XML
Via PROFINET, Ethernet/IP, Modbus TCP or PROFIBUS, a central controller can access the ET 200MP I/O modules in the same way as central I/O modules.
Communication is carried out fully automatically between the I/O controller in the central PLC and ET 200MP. Internal data transfer is interference-free on shielded cables.
Comprehensive, channel-specific diagnostics with plain text messages enables location and elimination of system faults in the shortest possible time. Annoying plant downtimes belong to the past, and availability is significantly increased.
Configuration, parameterization and diagnostics
ET 200MP can be configured and parameterized via TIA Portal (integrated as of V12.0). Alternatively using other configuration tools with a GSD file, see under this link.
Extensive diagnostics information is available to the user, depending on the selected I/O module. Please observe the functional limitations which may be present with the respective configuration tool.