P_KT01_XX_01995
SITOP 提供了全面的产品线,包括缓冲模块直至系统集成 DC UPS 单元,可针对电源提供保护,缓冲时间从数秒到几个小时。可根据所用的储能单元、相关环境条件、性能和功能进行选型。
选型表有助于针对具体应用找到适宜的 24 V 缓冲产品:
SITOP 24 V 缓冲模块
|
缓冲模块 1)
|
DC UPS,带电容器
|
DC UPS,带可充电电池
|
|
SITOP PSE201U
SITOP BUF1200
|
SITOP UPS500S
+ SITOP UPS501S 扩展模块
|
SITOP UPS1600
+ SITOP BAT1600 电池模块
|
SITOP UPS1600
+ SITOP UPS1100 电池模块
|
SITOP DC UPS
+电池模块
|
储能单元
|
|
|
|
|
|
24 V 缓冲,长达
|
240 s
|
分钟
|
小时
|
小时
|
小时
|
存储介质
|
电容器
|
双层电容器
|
凝胶电池(铅),磷酸铁锂 (LiFePO4) 电池
|
凝胶电池(铅),纯铅电池(纯铅)
|
凝胶电池,纯铅电池(纯铅)
|
电池使用寿命取决于温度。规定时间表示铅酸电池的原始容量下降到 80%。
|
0 … +50 °C: > 8 年
|
0 … +50 °C:> 8 年
|
铅:+20 ... +40 °C:铅:+20 … +40 °C:1 ... 1 年 (LiFePO4:+4 … +40 °C:11 ... 8 年)
|
铅:+20 ... +40 °C: 4 ... 1 年 (纯铅:+20 … +60 °C:> 10 ... 1 年)
|
铅:+20 ... +40 °C: 4 ... 1 年 (纯铅:+20 … +60 °C:> 10 ... 1 年)
|
电池的工作温度范围
|
-25 … +70 °C
|
0 … +60 °C
|
铅:-15 … +50 °C LiFePO4: -10 … +50 °C
|
Pb:-15 ... +50 °C 纯铅:-40 … +60 °C
|
Pb:-15 ... +50 °C 纯铅:-40 … +60 °C
|
容量选择
|
200 ... 300 ms/40 A
|
2.5 ... 20 kWs
|
PB:3.2 ... 228 Ah LiFePO4:2.5 ... 45 Ah
|
PB:1.2 ...72 Ah 纯铅:2.5 ... 15 Ah
|
PB:1.2 ...72 Ah 纯铅:2.5 ... 15 Ah
|
储能管理
|
无源
|
充电电流限制,缓冲准备就绪
|
温度控制充电,健康状态建模,缓冲准备就绪
|
温度控制充电,缓冲准备就绪
|
充电电流限制,缓冲准备就绪
|
需要通风
|
-
|
-
|
- LiFePO4
• 铅,纯铅
|
• 铅,纯铅
|
• 铅,纯铅
|
UPS 模块/电子装置
|
|
|
|
|
|
最大额定输出电流
|
40 A
|
15 A
|
40 A
|
40 A
|
40 A
|
最大动态过载电流
|
40 A (200 ms/300 ms)
|
25 A (200 ms)
|
120 A (30 ms) / 60 A (5 s/min)
|
120 A (30 ms) / 60 A (5 s/min)
|
56 A (80 ms)
|
接口
|
-
|
I/O、USB
|
I/O、USB、OPC UA,Ethernet/ PROFINET
|
I/O、USB、OPC UA,Ethernet/ PROFINET
|
I/O、串口、USB
|
有关运行和诊断的信息
|
|
|
|
|
|
|
-
|
•
|
•
|
•
|
•
|
|
-
|
•
|
•
|
•
|
•
|
|
-
|
-
|
•
|
•
|
-
|
|
-
|
-
|
•
|
•
|
-
|
|
-
|
-
|
•
|
•
|
-
|
|
-
|
-
|
•
|
•
|
-
|
|
-
|
-
|
•
|
•
|
-
|
关断多台 PC/PLC
|
-
|
-
|
•
|
•
|
-
|
从电池启动,无需交流电源(独立模式)
|
-
|
-
|
•
|
•
|
-
|
组态方式
|
|
|
|
|
|
|
-
|
•
|
•
|
•
|
•
|
|
-
|
-
|
•
|
•
|
-
|
|
-
|
-
|
•
|
•
|
-
|
|
-
|
-
|
•
|
•
|
-
|
防护等级
|
IP20
|
IP20
|
IP00
|
IP00
|
IP00
|
1) 关于技术数据,请见“附加模块/缓冲模块”项下的内容 http://www.siemens.com/sitop-buffering/mall
ENG_766133.xml
SITOP Manager - the tool for commissioning, engineering and monitoring of communication-capable SITOP power supplies
SITOP Manager is the medium for all users who do not work with SIMATIC STEP 7 in the TIA Portal or with SIMATIC PCS 7. It manages all communication-capable power supplies in a communication network and enables their commissioning, online and offline engineering and diagnostics, as well as operator control and monitoring. With the help of the SITOP Shutdown Service (autonomous function of the SITOP Manager), for example, it also supports continuous monitoring and specific shutdown of one or more PCs in case of a power failure. Data transmission is secure thanks to encrypted communication.
SITOP Manager is available as a free download in SIOS:
https://support.industry.siemens.com/cs/ww/en/view/109760607
SITOP Manager functions in conjunction with SITOP uninterruptible power supplies:
- Monitoring, diagnostics and shutdown for MS Windows for
- SITOP DC UPS modules with USB interface
- SITOP UPS500S
- Engineering, commissioning, monitoring, diagnostics and shutdown for
- SITOP UPS1600 PN / USB
- SITOP PSU8600 3 AC / 1 AC
SITOP Manager functions
- Integrated engineering, monitoring, diagnostics and service functions save time and operating costs
- Operation via the web interface simplifies automation projects
- Stability and quality prevent plant failures
- Shutting down specific PCs prevents data loss in the event of a power failure
- Since SITOP Manager supports Microsoft Windows and SIMATIC Industrial OS, it can be used on all common PCs
- Flexible usage options of the SITOP Manager due to usability on a wide range of terminal devices such as PC/industrial PCs, tablets, smartphones, etc.
- Secure, encrypted communication according to the Siemens security concepts ('Security-in-depth' model)
- Saving of plant downtimes through configuration changes even during operation
- The firmware update option ensures that the SITOP UPS1600 is always up-to-date
- Time, workload and cost savings through the configuration of multiple SITOP UPS1600 PNs/ USBs via one SITOP Manager project file
- Requirement for the use of the SITOP Manager with SITOP UPS1600 PN / USB:
- SITOP UPS1600 10 A, 20 A as of product state (PS) "6", firmware V2.2.2 and higher
- SITOP UPS1600 40 A as of product state (PS) "3", firmware V2.2.2 and higher
S_KT01_XX_00021
SITOP Manager UPS1600 offline, including saving of offline project to a project file
S_KT01_XX_00026
SITOP Manager UPS1600 Engineering SDS online