Overview
ENG_495603.XML
To comply with high requirements regarding installation and ambient conditions, SINAMICS S120 Cabinet Modules are also available in a liquid-cooled version.
The power loss of the units is transferred to the cooling liquid and dissipated, without noticeably increasing the temperature of the surrounding environment. As a consequence it is possible to save the expense of controlling the climate of the electrical room.
The system consists of liquid-cooled Basic Line Connection Modules, Active Line Connection Modules, Motor Modules, an Auxiliary Power Supply Module, and a suitably selected cooling unit (Heat Exchanger Module).
Basic Line Connection Modules
Basic Line Connection Modules comprise a Line Connection Module and a liquid-cooled Basic Line Module. Basic Line Connection Modules are only suitable for infeed operation, i.e. they are not capable of feeding regenerative energy back into the supply system.
If regenerative energy is produced, e.g. when the drives brake, it must be converted into heat in external braking resistors using a supplementary Motor Module, which is used as Braking Module.
When a Basic Line Connection Module is used as the infeed, a line reactor appropriate for the supply conditions must be installed. If the infeed is realized via a transformer with an appropriate rating in 6-pulse operation with a Basic Line Connection Module or in 12-pulse operation with two Basic Line Connection Modules, the line reactor is optional and can be omitted.
If two or more Basic Line Connection Modules are operated in parallel on a common supply system in order to increase power, then line reactors must also be used.
G_D213_XX_00105
Basic Line Connection Module ≤ 800 A
G_D213_XX_00106
Basic Line Connection Module > 800 A
Active Line Connection Modules
Active Line Connection Modules comprise a Line Connection Module, a liquid-cooled Active Interface Module and a liquid-cooled Active Line Module. Active Line Connection Modules can supply energy to the DC link and return regenerative energy to the line supply (energy recovery). The use of an additional Motor Module as a Braking Module is only required if the drives need to be decelerated in a controlled manner after a power failure (i.e. when energy cannot be fed back into the line supply).
In contrast to Basic Line Connection Modules, Active Line Connection Modules generate a regulated DC voltage which remains constant irrespective of fluctuations in the line voltage. However, in this case, the line voltage must remain within the permissible tolerance range. Active Line Connection Modules draw a virtually sinusoidal current from the supply system. Almost no harmonics occur. The total harmonic distortion factors of the current THD(I) and voltage THD(U) are typically in the range of approx. 3 % for rated current. THD(I) is calculated according to IEEE 519 (2014) and THD(U) according to IEC 61000-2-4 (2002). The stringent limit values of IEEE 519 (2014) are typically complied with.
Active Line Connection Modules always contain an Active Interface Module, which in addition to a Clean Power Filter, also includes the necessary pre-charging circuit for the Active Line Module.
G_D213_XX_00107
Active Line Connection Module with Active Interface Module and Active Line Module ≤800 A
G_D213_XX_00108
Active Line Connection Module with Active Interface Module and Active Line Module >800 A
Active Line Connection Modules compact
Active Line Connection Modules compact comprise a liquid-cooled Active Interface Module and a liquid-cooled Active Line Module. They can supply motoring energy to the DC link and return regenerative energy to the line supply. The line-side infeed via main switch with fuse switch disconnector or circuit breaker must be done on the plant side.
In contrast to Basic Line Connection Modules, Active Line Connection Modules compact generate a regulated DC voltage which remains constant irrespective of fluctuations in the line voltage. However, in this case, the line voltage must remain within the permissible tolerance range. Active Line Connection Modules compact draw a virtually sinusoidal current from the supply system. Almost no harmonics occur. The total harmonic distortion factors of the current THD(I) and voltage THD(U) are typically in the range of approx. 3 % for rated current. THD(I) is calculated according to IEEE 519 (2014) and THD(U) according to IEC 61000-2-4 (2002). The stringent limit values of IEEE 519 (2014) are typically complied with.
The line‑side infeed via main circuit breaker with fuse switch disconnector or circuit breaker must be carried out on the plant side.
G_D213_XX_00148
Active Line Connection Module compact with Active Interface Module and Active Line Module
Motor Modules
Each Cabinet Module is fitted with one SINAMICS S120 Motor Module in chassis format and covers the power range from 90 kW to 1500 kW (380 V to 480 V or 500 V to 690 V). The power rating can be extended up to approx. 5700 kW by connection in parallel.
The Motor Modules can also be used as Braking Modules (braking chopper) if a 3-phase braking resistor is connected instead of a motor.
Further information can be found in the SINAMICS Low Voltage Engineering Manual.
Motor Modules compact
Each Cabinet Module compact is fitted with one SINAMICS S120 Motor Module in chassis format and covers the power range from 90 kW to 1500 kW (380 V to 480 V or 500 V to 690 V). The power rating can be extended up to approx. 5700 kW by connection in parallel.
The Motor Modules compact can also be used as Braking Modules (braking chopper) if a 3‑phase braking resistor is connected instead of a motor.
Further information can be found in the SINAMICS Low Voltage Engineering Manual.
Auxiliary Power Supply Modules
Auxiliary Power Supply Modules supply power to the auxiliary power supply system of the SINAMICS S120 Cabinet Modules. The heat exchangers, which are installed in the SINAMICS S120 Cabinet Modules with degree of protection IP55, are one of the connections to the auxiliary power supply system. In addition, the auxiliary power supply system supplies the electronic modules with an external 24 V DC voltage. This is required when the DC link is not charged, for instance, in order to maintain PROFIBUS or PROFINET communication. The installation is analogous to the air-cooled Auxiliary Power Supply Modules with an additional water pipe system. The Auxiliary Power Supply Modules provide an expansion to the option K76 (auxiliary voltage generating unit) if higher power ratings are required.
Heat Exchanger Modules
Heat Exchanger Modules are used to dissipate the power loss from the converter. They comprise a deionized water circuit on the converter side and a raw water circuit on the plant side.
The hot deionized water in the circuit on the converter side passes through a low-maintenance circulating pump(s) into the water/water plate-type heat exchanger. This is made of stainless steel and connected to the raw water circuit on the plant side. The deionized water is cooled there by the raw water of the outer circuit and flows back into the drive.
Technical specifications
ENG_495605.XML
General technical specifications
Electrical specifications
|
Line voltages
|
380 ... 480 V 3 AC, ±10 % (-15 % <1 min)
500 … 690 V 3 AC, ±10 % (-15 % <1 min)
|
Line supply types
|
Grounded TN/TT systems and non-grounded IT systems
|
Line frequency
|
47 ... 63 Hz
|
Output frequency 1)
|
|
|
0 ... 550 Hz
|
|
0 ... 550 Hz
|
|
0 ... 550 Hz
|
Line power factor Fundamental
|
|
|
>0.96
|
|
Adjustable (factory-set to cos φ = 1)
|
Efficiency
|
|
|
>99 %
|
|
>97.5 % (including Active Interface Module)
|
|
>98.5 %
|
Overvoltage category
|
III acc. to EN 61800‑5‑1
|
Control method
|
Vector/Servo control with and without encoder or V/f control
|
Fixed speeds
|
15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal strip/PROFIBUS/PROFINET)
|
Skippable speed ranges
|
4, parameterizable
|
Setpoint resolution
|
0.001 r/min digital (14 bits + sign) 12 bits analog
|
Braking operation
|
With Active Line Modules, four-quadrant operation as standard (energy recovery). With Basic Line Modules, two-quadrant operation as standard, braking by means of a Motor Module.
|
Cabinet system
|
Cabinet system
|
Rittal TS 8, doors with double-barb lock, base plate with cable entry options
|
Paint finish
|
RAL 7035 (indoor requirements)
|
Mechanical specifications
|
Degree of protection
|
IP21 (higher degrees of protection up to IP55 optional)
|
Protection class
|
I acc. to EN 61800‑5‑1
|
Touch protection
|
EN 50274/DGUV regulation 3 when used as intended
|
Cooling method
|
Cooling in compliance with EN 60146:
Basic Line Connection Modules, Active Line Connection Modules, Motor Modules: WE - W: Liquid cooling - E: Forced air cooling, drive device outside the equipment
Line reactors, motor reactors, dv/dt filters with Voltage Peak Limiter: AN - A: Air cooling - N: Natural cooling (convection)
|
Ambient conditions
|
Storage 2)
|
Transport 2)
|
Operation
|
Ambient temperature
|
-25 ... +55 °C (-13 ... 131 °F)
|
-25 ... +70 °C (-13 ... +158 °F) from -40 °C (-40 °F) for 24 hours
|
0 ... +45 °C (32 ... 113°F) to +50 °C (122 °F) see derating data
|
Relative humidity
(condensation not permissible)
|
5 ... 95 %
Class 1K4 acc. to IEC 60721‑3‑1 (1997)
|
5 ... 95 % at 40 °C (104 °F) Class 2K3 acc. to IEC 60721‑3‑2 (1997)
|
5 ... 95 % Class 3K3 acc. to IEC 60721‑3‑3 (2002)
|
Environmental class/harmful chemical substances
|
Class 1C2 acc. to EN 60721‑3‑1 (1997)
|
Class 2C2 acc. to EN 60721‑3‑2 (1997)
|
Class 3C2 acc. to EN 60721‑3‑3 (2002)
|
Organic/biological influences
|
Class 1B1 acc. to EN 60721‑3‑1 (1997)
|
Class 2B1 acc. to EN 60721‑3‑2 (1997)
|
Class 3B1 acc. to EN 60721‑3‑3 (2002)
|
Mechanically active substances
|
Class 1S1 acc. to EN 60721‑3‑1 (1997)
|
Class 2S1 acc. to EN 60721‑3‑2 (1997)
|
Class 3S1 acc. to EN 60721‑3‑3 (2002)
|
Degree of pollution
|
2 acc. to IEC/EN 61800‑5‑1
|
Installation altitude
|
≤ 2000 m (6562 ft) above sea level without derating; > 2000 m (6562 ft)see derating data
|
Mechanical stability
|
Storage 2)
|
Transport 2)
|
Operation
|
Vibratory load
|
Class 1M2 acc. to EN 60721‑3‑1 (1997)
|
Class 2M2 acc. to EN 60721‑3‑2 (1997)
|
–
|
|
1.5 mm (0.06 in) at 5 ... 9 Hz
|
3.1 mm (0.12 in) at 5 ... 9 Hz
|
0.075 mm (0.003 in) at 10 ... 58 Hz
|
|
5 m/s² (16.4 ft/s²) at >9 ... 200 Hz
|
10 m/s² (32.8 ft/s²) at >9 ... 200 Hz
|
9.8 m/s² (32.2 ft/s²) at >58 ... 200 Hz
|
Shock load
|
Class 1M2 acc. to EN 60721‑3‑1 (1997)
|
Class 2M2 acc. to EN 60721‑3‑2 (1997)
|
Class 3M1 acc. to EN 60721‑3‑3 (2002)
|
|
40 m/s² (131 ft/s²) at 22 ms
|
100 m/s² (328 ft/s²) at 11 ms
|
Test values acc. to EN 60068‑2‑27
test Ea: 5 g, 30 ms, 3 shocks
|
Compliance with standards
|
Conformances/certificates of suitability, according to
|
CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC for functional safety)
RCM, RoHS II, UKCA, marine certification DNV, ABS, CCS (Type approval, only in combination with the Option M66) Green Passport: Option B50 creates a form for the material declaration according to Green Passport.
|
Radio interference suppression
|
SINAMICS converter systems are not designed for connection to the public grid (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800‑3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public grid.
|
1) Higher output frequencies available on request.
2) In transport packaging.
Deviations from the specified class are underlined.
Cooling circuit and coolant quality
The following tables and sections describe the coolant quality requirements for the raw water circuit on the plant side and the deionized water circuit of the liquid-cooled SINAMICS S120 Cabinet Modules on the converter side.
The coolant consists of a coolant basis and an additional antifreeze agent or inhibitor. See "Antifreeze and inhibitors".
Plant-side raw water circuit (based on VDI 3803)
|
- System pressure with reference to atmospheric pressure, max.
|
600 kPa
|
- Inlet temperature of liquid coolant
|
Antifreeze essential for temperature range between 0 °C (32 °F) and 5 °C (41 °F)
|
- Degree of protection <IP55
|
0 ... 38 °C (32 ... 104 °F) without derating >38 ... 43 °C (104 ... 131 °F), see derating characteristics
|
- Degree of protection IP55
|
0 ... 33 °C (32 ... 104 °F) without derating >33 ... 38 °C (104 ... 131 °F), see derating characteristics
|
Coolant quality
|
|
|
< 2200 μS/cm
|
|
7.5 ... 9
|
|
< 180 mg/l
|
|
<200 mg/l
|
|
<50 mg/l
|
|
< 3 mg/l
|
|
< 0.2 mg/l
|
|
< 50 CFU/ml
|
|
< 47 mg/l
|
|
< 2.65 mg/l
|
|
< 4 mg/l
|
|
< 20 (< 40 °C (104 °F)) °dH
|
- Size of entrained particles
|
≤ 0.5 mm (0.02 in)
|
- SK 4.3 (upper limit value of polymer phosphates for untreated additional water)
|
< 10 mmol/l
|
- Permissible limit values for suspended particles in the coolant
|
No deposits of solid particles at ≥ 0.5 m/s
|
Converter-side deionized water circuit
|
- System pressure with reference to atmospheric pressure, max.
|
600 kPa
|
- Pressure drop at rated volumetric flow
|
70 kPa
|
- Recommended pressure range
|
80 ... 150 kPa (is applicable for water as coolant)
|
- Inlet temperature of liquid coolant
|
Depending on ambient temperature; no condensation permitted
Antifreeze essential for temperature range between 0 °C (32 °F) and 5 °C (41 °F)
|
- Degree of protection <IP55
|
0 ... 45 °C (32 ... 113 °F) without derating >45 ... 50 °C (113 ... 122 °F), see derating characteristics
|
- Degree of protection IP55
|
0 ... 40 °C (32 ... 104 °F) without derating >40 ... 45 °C (104 ... 113 °F), see derating characteristics
|
Coolant quality
|
|
Distilled, demineralized, completely desalinated water or deionized water with reduced electrical conductivity ISO 3696, quality 3 or based on IEC 60993
|
- Electrical conductivity when filling
|
<30 μS/cm (3 mS/m)
|
|
5 ... 8
|
- Components that can be oxidized as oxygen content
|
<30 mg/l
|
- Residue after vaporization and drying at 110 °C (230 °F)
|
<10 mg/kg
|
The coolant definition specified here should only be considered as recommendation. For units that have been shipped, the information and data provided in the equipment manual supplied should be observed!
Antifreeze and inhibitors
Antifreeze
|
Antifrogen N
|
Antifrogen L
|
DOWCAL 100
|
Manufacturer
|
Clariant
|
Clariant
|
DOW
|
Chemical base
|
Ethylene glycol
|
Propylene glycol
|
Ethylene glycol
|
Minimum concentration
|
25 %
|
25 %
|
25 %
|
Antifreeze agent with minimum concentration
|
-10 °C (14 °F)
|
-10 °C (14 °F)
|
-10 °C (14 °F)
|
Maximum concentration
|
45 %
|
48 %
|
45 %
|
Antifreeze agent with maximum concentration
|
-30 °C (-22 °F)
|
-30 °C (-22 °F)
|
-30 °C (-22 °F)
|
Inhibitor content
|
Contains inhibitors with nitrites
|
Contains inhibitors that are free of nitrites, amines, borates, and phosphate
|
Contains inhibitors that are free of nitrites, amines, and phosphate
|
Biocide action with a concentration of
|
>25 %
|
>25 %
|
>25 %
|
Biocides prevent corrosion that is caused by slime-forming, corrosive or iron-depositing bacteria. These can occur in closed cooling circuits with low water hardness and in open cooling circuits. Biocides must always be selected according to the relevant bacterial risks. Compatibility with inhibitors or antifreeze used with them must be checked on a case-by-case basis.
Inhibitors
|
Antifrogen N
|
ANTICORIT S 2000 AA
|
Manufacturer
|
Clariant
|
Fuchs
|
Chemical base
|
Ethylene glycol
|
-
|
Minimum concentration
|
25 %
|
3 %
|
Maximum concentration
|
45 %
|
5 %
|
Recommended service
The manufacturer of the antifreeze/inhibitor should analyze the coolant at least once per annum. The concentration and boundary conditions of the antifreeze/inhibitor should be checked. It may be necessary to correct the concentration on the plant side.
Protection against condensation
With liquid-cooled units, warm air can condense on the cold surfaces of heat sinks, pipes and hoses. This condensation depends on the air humidity and the temperature difference between the ambient air and the coolant.
The water which is produced as a result of condensation can cause corrosion as well as electrical damage such as creepage shorts and flashovers. As the SINAMICS units cannot prevent condensation if it is caused by the prevailing climatic conditions, any potential risk of condensation must be prevented by appropriate engineering or by precautionary measures implemented by the customer. These measures include the following:
- a fixed coolant temperature that has been adjusted to the expected air humidity or ambient temperature ensures that critical differences between the coolant and ambient air temperatures do not develop or
- temperature regulation of the coolant as a function of the ambient air temperature
The temperature at which water vapor contained in the air condenses into water is known as the dew point. In order to reliably prevent condensation, the coolant temperature must always be higher than the dew point.
The table below specifies the dew point as a function of room temperature T and relative air humidity Φ for an atmospheric pressure of 100 kPa (1 bar). This corresponds to an installation altitude of 0 to approximately 500 m above sea level. Since the dew point drops as the air pressure decreases, the dew point values at higher installation altitudes are lower than the specified table values. It is therefore the safest approach to engineer the coolant temperature according to the table values for an installation altitude of zero.
Indication of dew point temperature / coolant temperature
Room temperature
|
Relative air humidity Φ
|
T
|
20 %
|
30 %
|
40 %
|
50 %
|
60 %
|
70 %
|
80 %
|
85 %
|
90 %
|
95 %
|
100 %
|
10 °C (50 °F)
|
<0 °C (<32 °F)
|
<0 °C (<32 °F)
|
<0 °C (<32 °F)
|
0.2 °C (32.4 °F)
|
2.7 °C (36.9 °F)
|
4.8 °C (40.6 °F)
|
6.7 °C (44.1 °F)
|
7.6 °C (45.7 °F)
|
8.4 °C (47.1 °F)
|
9.2 °C (48.6 °F)
|
10 °C (50 °F)
|
20 °C (68 °F)
|
<0 °C (<32 °F)
|
2 °C (35.6 °F)
|
6 °C (42.8 °F)
|
9.3 °C (48.7 °F)
|
12 °C (53.6 °F)
|
14.3 °C (57.7 °F)
|
16.4 °C (61.5 °F)
|
17.4 °C (63.3 °F)
|
18.3 °C (64.9 °F)
|
19.1 °C (66.4 °F)
|
20 °C (68 °F)
|
25 °C (77 °F)
|
0.6 °C (33.1 °F)
|
6.3 °C (43.3 °F)
|
10.5 °C (50.9 °F)
|
13.8 °C (56.8 °F)
|
16.7 °C (62.1 °F)
|
19.1 °C (66.4 °F)
|
21.2 °C (70.2 °F)
|
22.2 °C (72.0 °F)
|
23.2 °C (73.8 °F)
|
24.1 °C (75.4 °F)
|
24.9 °C (76.8 °F)
|
30 °C (86 °F)
|
4.7 °C (40.5 °F)
|
10.5 °C (50.9 °F)
|
14.9 °C (58.8 °F)
|
18.4 °C (65.1 °F)
|
21.3 °C (70.3 °F)
|
23.8 °C (74.8 °F)
|
26.1 °C (79.0 °F)
|
27.1 °C (80.8 °F)
|
28.1 °C (82.6 °F)
|
29 °C (84.2 °F)
|
29.9 °C (85.8 °F)
|
35 °C (95 °F)
|
8.7 °C (47.7 °F)
|
14.8 °C (58.6 °F)
|
19.3 °C (66.7 °F)
|
22.9 °C (73.2 °F)
|
26 °C (78.8 °F)
|
28.6 °C (83.5 °F)
|
30.9 °C (87.6 °F)
|
32 °C (89.6 °F)
|
33 °C (91.4 °F)
|
34 °C (93.2 °F)
|
34.9 °C (94.8 °F)
|
40 °C (104 °F)
|
12.8 °C (55.0 °F)
|
19.1 °C (66.4 °F)
|
23.7 °C (74.7 °F)
|
27.5 °C (81.5 °F)
|
30.6 °C (87.1 °F)
|
33.4 °C (92.1 °F)
|
35.8 °C (96.4 °F)
|
36.9 °C (98.4 °F)
|
37.9 °C (100 °F)
|
38.9 °C (102 °F)
|
39.9 °C (104 °F)
|
45 °C (113 °F)
|
16.8 °C (62.2 °F)
|
23.3 °C (73.9 °F)
|
28.2 °C (82.8 °F)
|
32 °C (89.6 °F)
|
35.3 °C (95.5 °F)
|
38.1 °C (101 °F)
|
40.6 °C (105 °F)
|
41.8 °C (107 °F)
|
42.9 °C (109 °F)
|
43.9 °C (111 °F)
|
44.9 °C (113 °F)
|
50 °C (122 °F)
|
20.8 °C (69.4 °F)
|
27.5 °C (81.5 °F)
|
32.6 °C (90.7 °F)
|
36.6 °C (97.9 °F)
|
40 °C (104 °F)
|
42.9 °C (109 °F)
|
45.5 °C (114 °F)
|
46.6 °C (116 °F)
|
47.8 °C (118 °F)
|
48.9 °C (120 °F)
|
49.9 °C (122 °F)
|
A detailed description of the cooling circuits and the recommended coolant is given in the SINAMICS Low Voltage Engineering Manual.
Characteristic curves
ENG_495608.XML
Derating
Liquid-cooled SINAMICS S120 Cabinet Modules are rated for an ambient temperature of 45 °C and installation altitudes up to 2000 m above sea level and a plant-side raw water temperature of 38 °C (<IP55) or 33 °C (IP55). At ambient temperatures > 45 °C and a plant-side raw water temperature > 38 °C (<IP55) or 33 °C (IP55), the output current must be reduced. Ambient temperatures above 50 °C are not permissible. At installation altitudes > 2000 m above sea level, it must be taken into account that the air pressure, and therefore air density, decreases as the height increases. As a consequence, the cooling efficiency and the insulation capacity of the air also decrease.
At installation altitudes above 2000 m, the line voltage must not exceed certain limits in order to be able to isolate the surge voltages according to IEC 61800‑5‑1 for overvoltage category III. If the line voltage is above this limit at installation altitudes > 2000 m, measures must be taken to reduce the transient overvoltages of Category III to values of Category II, e. g. supply of the devices via an isolating transformer.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
The intake temperatures in the plant/system side raw water circuit must always be at least 7 K below the intake temperatures in the converter-side deionized water circuit. This ensures that the cooling power of the Heat Exchanger Module of the deionized water circuit, specified in the technical data, can be dissipated to the raw water circuit.
In order to prevent condensation, the inlet temperature of the liquid coolant should be kept above the ambient temperature depending on the relative air humidity.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
G_D213_XX_00109
Current derating as a function of the temperature of the cooling liquid in the converter-side deionized water circuit 1), The inlet temperature of the liquid coolant depends on the ambient temperature, no condensation permitted.2)
G_D213_XX_00038
Current derating as a function of ambient temperature 1)
1) The factors of the two derating curves must not be multiplied. The highest value in each case must be assumed for the purposes of calculation, so that the derating factor in the worst-case scenario is 0.9.
G_D213_XX_00072
Permissible ambient temperature as a function of installation altitude
Current derating as a function of the pulse frequency
To reduce motor noise or to increase output frequency, the pulse frequency can be increased relative to the factory setting (1.25 kHz or 2 kHz). When the pulse frequency is increased, the derating factor of the output current must be taken into account. This derating factor must be applied to the currents specified in the technical data.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
The following table lists the rated output currents of the Motor Modules with pulse frequency set at the factory as well as the current derating factors (permissible output currents referred to the rated output current) for higher pulse frequencies.
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Motor Module
|
Type rating at 400 V
|
Output current at 2 kHz
|
Derating factor at pulse frequency
|
6SL3725-...
|
kW
|
A
|
2.5 kHz
|
4 kHz
|
5 kHz
|
7.5 kHz
|
8 kHz
|
380 ... 480 V 3 AC / 510 ... 720 V DC
|
1TE32-1AA3
|
110
|
210
|
95 %
|
82 %
|
74 %
|
54 %
|
50 %
|
1TE32-6AA3
|
132
|
260
|
95 %
|
83 %
|
74 %
|
54 %
|
50 %
|
1TE33-1AA3
|
160
|
310
|
97 %
|
88 %
|
78 %
|
54 %
|
50 %
|
1TE35-0AA3
|
250
|
490
|
94 %
|
78 %
|
71 %
|
53 %
|
50 %
|
1TE41-4AS3 1)
|
800
|
1330
|
88 %
|
55 %
|
–
|
–
|
–
|
1) This Motor Module has been specifically designed for loads demanding a high dynamic performance. The derating factor kIGBT and the derating characteristics can be ignored (see section “Duty cycles” in the SINAMICS Low Voltage Engineering Manual).
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 1.25 kHz
Motor Module
|
Type rating at 400 V or 690 V
|
Output current at 1.25 kHz
|
Derating factor at pulse frequency
|
6SL3725-...
|
kW
|
A
|
2 kHz
|
2.5 kHz
|
4 kHz
|
5 kHz
|
7.5 kHz
|
8 kHz
|
380 ... 480 V 3 AC / 510 ... 720 V DC
|
|
1TE36-1AA3
|
315
|
605
|
83 %
|
72 %
|
64 %
|
60 %
|
40 %
|
36 %
|
1TE37-5AA3
|
400
|
745
|
87 %
|
79 %
|
64 %
|
55 %
|
40 %
|
37 %
|
1TE38-4AA3
|
450
|
840
|
87 %
|
79 %
|
64 %
|
55 %
|
40 %
|
37 %
|
1TE41-0.A3
|
560
|
985
|
92 %
|
87 %
|
70 %
|
60 %
|
50 %
|
47 %
|
1TE41-2.A3
|
710
|
1260
|
97 %
|
95 %
|
74 %
|
60 %
|
50 %
|
47 %
|
1TE41-4.A3
|
800
|
1405
|
97 %
|
95 %
|
74 %
|
60 %
|
50 %
|
47 %
|
500 ... 690 V 3 AC / 675 ... 1035 V DC
|
|
1TG31-0AA3
|
90
|
100
|
92 %
|
88 %
|
71 %
|
60 %
|
40 %
|
-
|
1TG31-5AA3
|
132
|
150
|
90 %
|
84 %
|
66 %
|
55 %
|
35 %
|
-
|
1TG32-2AA3
|
200
|
215
|
92 %
|
87 %
|
70 %
|
60 %
|
40 %
|
-
|
1TG33-3AA3
|
315
|
330
|
89 %
|
82 %
|
65 %
|
55 %
|
40 %
|
-
|
1TG34-7AA3
|
450
|
465
|
92 %
|
87 %
|
67 %
|
55 %
|
35 %
|
-
|
1TG35-8AA3
|
560
|
575
|
91 %
|
85 %
|
64 %
|
50 %
|
35 %
|
-
|
1TG37-4AA3
|
710
|
735
|
84 %
|
74 %
|
53 %
|
40 %
|
25 %
|
-
|
1TG38-0AA3
|
800 1)
|
810
|
82 %
|
71 %
|
52 %
|
40 %
|
25 %
|
-
|
1TG38-1.A3
|
800
|
810
|
97 %
|
95 %
|
71 %
|
55 %
|
35 %
|
-
|
1TG41-0.A3
|
1000
|
1025
|
91 %
|
86 %
|
64 %
|
50 %
|
30 %
|
-
|
1TG41-3.A3
|
1200
|
1270
|
87 %
|
79 %
|
55 %
|
40 %
|
25 %
|
-
|
1TG41-6.P3
|
1500
|
1560
|
87 %
|
79 %
|
55 %
|
40 %
|
25 %
|
-
|
1) The Motor Module 6SL3725-1TG38-0AA3 is optimized for low overload; with an increased pulse frequency, the derating factor is higher than for the Motor Module 6SL3725-1TG38-1AA3.
The following tables list the maximum achievable output frequency as a function of the pulse frequency:
Maximum output frequencies achieved by increasing the pulse frequency
The adjustable pulse frequencies – and therefore the output frequencies that can be achieved with the factory-set current controller clock cycles – are listed below.
Current controller clock cycle TI
|
Adjustable pulse frequency fp
|
Max. achievable output frequency fA
|
V/f mode
|
Vector mode
|
Servo mode
|
250 µs 1)
|
2 kHz
|
166 Hz
|
166 Hz
|
333 Hz
|
4 kHz
|
333 Hz
|
333 Hz
|
550 Hz 3)
|
8 kHz
|
550 Hz 3)
|
480 Hz
|
550 Hz 3)
|
400 µs 2)
|
1.25 kHz
|
104 Hz
|
104 Hz
|
–
|
2.5 kHz
|
208 Hz
|
208 Hz
|
–
|
5.0 kHz
|
416 Hz
|
300 Hz
|
–
|
7.5 kHz
|
550 Hz 3)
|
300 Hz
|
–
|
1) As factory setting, the following devices have a current controller clock cycle of 250 µs and a pulse frequency of 2 kHz: - 510 ... 720 V DC: ≤ 250 kW / 490 A, 6SL3725-1TE41-4AS5
2) As factory setting, the following devices have a current controller clock cycle of 400 µs and a pulse frequency of 1.25 kHz: - 510 ... 720 V DC: ≥ 315 kW / 605 A, except 6SL3725-1TE41-4AS5, - 675 ... 1035 V DC: All power ratings
3) With the "High output frequencies" license, which can be ordered as option J01 on the CompactFlash card for SINAMICS S120, the maximum output frequency is increased up to 650 Hz. For more information, see https://support.industry.siemens.com/cs/document/104020669
Overload capability
SINAMICS S120 Cabinet Modules have an overload reserve, e.g. to handle breakaway torques. If larger surge loads occur, this must be taken into account in the configuration. For drives with overload requirements, the appropriate base load current must, therefore, be used as a basis for the required load.
Permissible overload assumes that the converter is operated at its base-load current before and after the overload occurs, based on a duty cycle duration of 300 s.
Another precondition is that the Motor Modules are operated at their factory-set pulse frequency at output frequencies >10 Hz.
For temporary, periodic duty cycles with high variations of load within the duty cycle, the relevant sections of the SINAMICS Low Voltage Engineering Manual must be observed.
Motor Modules
Motor Modules can be configured on the basis of different base load currents.
The base-load current for a low overload IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s.
G_D213_XX_00035
Low overload
The base-load current IH for a high overload is based on a load cycle of 150 % for 60 s or 160 % for 10 s.
G_D213_XX_00036
High overload
The following applies to the Motor Module 6SL3725-1TG41-6.P3:
This Motor Module is particularly suited to high breakaway torques with applications such as drilling, mixers, centrifuges, and test bays. An additional duty cycle is required at output frequencies of 5 Hz to 10 Hz.
At output frequencies of 1 Hz to 5 Hz, the short-time current is 1900 A for 5 s.
G_D213_XX_00116
High overload for Motor Module 6SL3725-1TG41-6.P3
Basic Line Connection Modules and Active Line Connection Modules
The base-load current for a high overload IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s.
G_D213_XX_00079
High overload